Our own factory in China manufactures oil-immersed and dry-type transformers, plus switchgear, for contractors and distributors across Central Asia and Africa. Standard ratings, straightforward pricing, no tenders.
Our transformers are built at our own factory in China, Henan Wanjin Electrical Equipment Co., Ltd., in operation since 2006. The factory handles production, routine testing before shipment and warranty. DailyENS, founded in 2022 and grown out of the factory's export business, handles export quotations, contracts, documentation, shipment coordination and after-sales communication. DailyENS orders receive guaranteed production priority, with a current capacity of 300+ transformer units per month.
See inside our factory →Every transformer ships with its factory routine test report as standard, covering the applicable routine tests for that unit — winding resistance, voltage ratio and vector group, short-circuit impedance and load loss, no-load loss and no-load current, insulation resistance, and dielectric (withstand voltage) tests.
Can't visit in person? We can arrange a live video walkthrough of the factory, share production progress videos for your specific order, and provide video of the test/inspection process before shipment.
Distribution-class equipment manufactured to IEC/GB design practice. For projects requiring full tender-scale type-test certification, talk to us first.
Our own manufacturing base comes first. When a project needs a different specification, voltage class or product category we don't directly produce, we draw on a wider network of manufacturing partners across China to provide a suitable solution. In these cases, DailyENS manages the order and stays involved in specification matching, quality verification and shipment coordination, while production is carried out independently by the partner factory. Every equipment issue is DailyENS's responsibility to resolve, whether it comes from our own manufacturing base or our wider network.
Silicon-steel core lamination and copper winding, produced at our own manufacturing base — the same process used for every transformer we ship, with our team directly involved in production planning and quality control at every stage.
Sealed-tank distribution transformers for outdoor pole/pad-mount installation.
Cast-resin transformers for indoor, fire-sensitive or maintenance-light sites.
Ring main units and low-voltage panels to pair with your transformer order.
Typical values from our standard catalogue; final specifications are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | No-load current (%) | Vector group |
|---|---|---|---|---|---|
| 30 | 100 | 630 | 4 | 2.3 | Dyn11 / Yyn0 |
| 50 | 130 | 910 | 4 | 2.0 | Dyn11 / Yyn0 |
| 80 | 180 | 1310 | 4 | 1.9 | Dyn11 / Yyn0 |
| 100 | 200 | 1580 | 4 | 1.8 | Dyn11 / Yyn0 |
| 160 | 280 | 2310 | 4 | 1.6 | Dyn11 / Yyn0 |
| 200 | 340 | 2730 | 4 | 1.5 | Dyn11 / Yyn0 |
| 250 | 400 | 3200 | 4 | 1.4 | Dyn11 / Yyn0 |
| 315 | 480 | 3830 | 4 | 1.4 | Dyn11 / Yyn0 |
| 400 | 570 | 4520 | 4 | 1.3 | Dyn11 / Yyn0 |
| 500 | 680 | 5410 | 4 | 1.2 | Dyn11 / Yyn0 |
| 630 | 810 | 6200 | 4.5 | 1.1 | Dyn11 / Yyn0 |
| 800 | 980 | 7500 | 4.5 | 1.0 | Dyn11 / Yyn0 |
| 1000 | 1150 | 10300 | 4.5 | 1.0 | Dyn11 / Yyn0 |
| 1250 | 1360 | 12000 | 4.5 | 0.9 | Dyn11 / Yyn0 |
| 1600 | 1640 | 14500 | 4.5 | 0.8 | Dyn11 / Yyn0 |
Rated capacity 30 – 1600 kVA. Dyn11 and Yyn0 are both available. Rated capacity 20–2500 kVA is standard. The table lists the ratings with catalogue data; other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) — G1: Grade-1 · G2: Grade-2 | Short-circuit impedance (%) | No-load current (%) | Vector group |
|---|---|---|---|---|---|
| 30 | 80 | G1 550/480 · G2 630/600 | 4 | 1.4 | Yyn0 / Dyn11 |
| 50 | 100 | G1 730/695 · G2 910/870 | 4 | 1.2 | Yyn0 / Dyn11 |
| 63 | 110 | G1 870/830 · G2 1090/1040 | 4 | 0.97 | Yyn0 / Dyn11 |
| 80 | 130 | G1 1050/1000 · G2 1310/1250 | 4 | 0.97 | Yyn0 / Dyn11 |
| 100 | 150 | G1 1265/1200 · G2 1580/1500 | 4 | 0.97 | Yyn0 / Dyn11 |
| 125 | 170 | G1 1510/1440 · G2 1890/1800 | 4 | 0.84 | Yyn0 / Dyn11 |
| 160 | 200 | G1 1850/1760 · G2 2310/2200 | 4 | 0.84 | Yyn0 / Dyn11 |
| 200 | 240 | G1 2185/2080 · G2 2730/2600 | 4 | 0.74 | Yyn0 / Dyn11 |
| 250 | 290 | G1 2560/2440 · G2 3200/3050 | 4 | 0.64 | Yyn0 / Dyn11 |
| 315 | 340 | G1 3065/2920 · G2 3830/3650 | 4 | 0.64 | Yyn0 / Dyn11 |
| 400 | 410 | G1 3615/3440 · G2 4520/4300 | 4 | 0.54 | Yyn0 / Dyn11 |
| 500 | 480 | G1 4330/4120 · G2 5410/5150 | 4 | 0.54 | Yyn0 / Dyn11 |
| 630 | 570 | G1 4960 · G2 6200 | 4.5 | 0.54 | Yyn0 / Dyn11 |
| 800 | 700 | G1 6000 · G2 7500 | 4.5 | 0.48 | Yyn0 / Dyn11 |
| 1000 | 830 | G1 8240 · G2 10300 | 4.5 | 0.42 | Yyn0 / Dyn11 |
| 1250 | 970 | G1 9600 · G2 12000 | 4.5 | 0.36 | Yyn0 / Dyn11 |
| 1600 | 1170 | G1 11600 · G2 14500 | 4.5 | 0.36 | Yyn0 / Dyn11 |
Rated capacity 30 – 1600 kVA. No-load loss Grade-1 and Grade-2 are identical in the factory data; load loss is shown as G1 · G2 (Grade-1 / Grade-2). For ratings up to 500 kVA each pair is upper = Dyn11, lower = Yyn0. Rated capacity 20–2500 kVA is standard. The table lists the ratings with catalogue data; other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 540 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 620 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 720 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 880 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 980 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 1160 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1340 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1300 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1520 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1770 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 2090 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 2450 | 11730 | 6 | D,yn11 / Y,yn0 |
| 2000 | 3050 | 14450 | 6 | D,yn11 / Y,yn0 |
| 2500 | 3600 | 17170 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 480 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 550 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 640 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 790 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 880 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 1040 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1200 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1170 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1360 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1590 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1880 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 2200 | 11700 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2740 | 14400 | 6 | D,yn11 / Y,yn0 |
| 2500 | 3240 | 17100 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 430 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 495 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 575 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 705 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 785 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 930 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1070 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1040 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1210 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1410 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1670 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 1960 | 11700 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2440 | 14400 | 6 | D,yn11 / Y,yn0 |
| 2500 | 2880 | 17100 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 385 | 1910 | 4 | D,yn11 / Y,yn0 |
| 200 | 445 | 2270 | 4 | D,yn11 / Y,yn0 |
| 250 | 515 | 2480 | 4 | D,yn11 / Y,yn0 |
| 315 | 635 | 3120 | 4 | D,yn11 / Y,yn0 |
| 400 | 705 | 3590 | 4 | D,yn11 / Y,yn0 |
| 500 | 835 | 4390 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 965 | 5290 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 935 | 5360 | 6 | D,yn11 / Y,yn0 |
| 800 | 1090 | 6260 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1270 | 7310 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1500 | 8720 | 6 | D,yn11 / Y,yn0 |
| 1600 | 1760 | 10500 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2190 | 13000 | 6 | D,yn11 / Y,yn0 |
| 2500 | 2590 | 15400 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
Swipe horizontally to see all columns →
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | No-load current (%) |
|---|---|---|---|---|
| 50 | 188 | 1210 | 6.5 | 1.8 |
| 100 | 232 | 2010 | 6.5 | 1.9 |
| 125 | 272 | 2380 | 6.5 | 1.7 |
| 160 | 298 | 2860 | 6.5 | 1.6 |
| 200 | 344 | 3330 | 6.5 | 1.5 |
| 250 | 398 | 3960 | 6.5 | 1.4 |
| 315 | 478 | 4780 | 6.5 | 1.3 |
| 400 | 564 | 5740 | 6.5 | 1.2 |
| 500 | 692 | 6880 | 6.5 | 1.1 |
| 630 | 810 | 8280 | 6.5 | 1.0 |
| 800 | 942 | 9640 | 6.5 | 0.9 |
| 1000 | 1150 | 11520 | 6.5 | 0.8 |
| 1250 | 1390 | 13960 | 6.5 | 0.7 |
| 1600 | 1670 | 16860 | 6.5 | 0.6 |
| 2000 | 1940 | 23000 | 6.5 | 0.8 |
| 2500 | 2300 | 27300 | 6.5 | 0.7 |
| 3150 | 2680 | 32900 | 7.0 | 0.7 |
| 4000 | 3240 | 38900 | 7.0 | 0.6 |
| 5000 | 3870 | 46400 | 7.0 | 0.6 |
| 6300 | 4560 | 56200 | 7.5 | 0.6 |
| 8000 | 4810 | 70700 | 7.5 | 0.5 |
| 10000 | 5860 | 83200 | 7.5 | 0.5 |
| 12500 | 6880 | 98400 | 8 | 0.5 |
| 16000 | 7020 | 131700 | 8 | 0.4 |
| 20000 | 8270 | 155700 | 8 | 0.4 |
Rated capacity 50 – 20000 kVA. Short-circuit impedance follows the factory data.
Other series in the factory programme: S18, S22, SCB14, SCB18.
Kenya · Tanzania · Nigeria · Cote D'Ivoire · Uganda · Ethiopia · Ghana · Zambia · Mozambique · Cameroon · Senegal · Zimbabwe · Egypt · Morocco · Algeria · Sudan · Kazakhstan · Uzbekistan · Kyrgyzstan · Tajikistan · Turkmenistan
Nigeria · Kenya · Kazakhstan · Uzbekistan
We'd rather tell you upfront than take an order we can't properly fulfill:
Have detailed specifications, drawings, or other files to share? Email us directly at [email protected]
Last updated: September 22, 2026
When you use our quote tools or contact us we collect the details you give us — name, email, phone/WhatsApp, country/city, your electricity usage and price, company name and any business licence/registration number you choose to provide, plus the content of your messages. When you browse we automatically collect page views, events, device/browser information, an approximate (city-level) location derived from your IP address, and — only with your consent — a pseudonymous analytics identifier stored in a cookie. Read the full privacy policy for the complete list and the purposes.
To prepare quotes, answer enquiries, follow up on orders and installation, improve the website, and meet our legal obligations. We never sell your personal information. Full details.
Essential cookies are needed to run the site. Analytics cookies are only set after you choose Accept all — if you choose Essential only (or close this banner) no analytics cookie is written.
| Cookie | Category | Purpose | Duration | Consent required |
|---|---|---|---|---|
_ga |
Analytics | Tells one visitor apart from another for aggregate traffic statistics. | 2 years by default | Yes |
_ga_JRCS1TC26Y |
Analytics | Keeps the session/visit state for this GA4 property. | 2 years by default | Yes |
We use Google Analytics 4 to measure visits and understand which pages are useful. Google acts as a data processor for us. Your IP address is transmitted to Google so it can derive an approximate location, but GA4 standard properties do not log or store IP addresses. Google signals are not enabled. Event-level data is kept for 14 months in our GA4 property. If you decline analytics cookies, the analytics cookie is not written and analytics storage stays denied.
You can access, correct or delete your personal information, restrict or object to processing, request portability, withdraw consent at any time, and lodge a complaint with your supervisory authority. Contact [email protected]. Full details.
Use Cookie settings (in this banner, at the bottom of every page, or on the privacy policy page) to change your selection — it takes effect immediately.