Power Equipment
Typical values from our standard catalogue; final specifications are confirmed in the technical offer.
10/11 kV: 20–2500 kVA · 35 kV: 50–20000 kVA
Sealed-tank distribution transformers for outdoor pole/pad-mount installation.
10/11 kV: 30–2500 kVA
Cast-resin transformers for indoor, fire-sensitive or maintenance-light sites.
RMU & LV panel · up to 35 kV
Ring main units and low-voltage panels to pair with your transformer order.
| Series | Type | Voltage class | Catalogue table | Vector group |
|---|---|---|---|---|
| S11 | Oil-immersed | 10/11 kV | 30–1600 kVA | Dyn11 / Yyn0 |
| S13 | Oil-immersed | 10/11 kV | 30–1600 kVA (loss grades G1 / G2) | Yyn0 / Dyn11 |
| SCB10 · SCB11 · SCB12 · SCB13 | Dry-type (cast-resin) | 10 kV | 160–2500 kVA | D,yn11 / Y,yn0 |
| SZ11 | Oil-immersed, on-load tap-changing | 35 kV | 50–20000 kVA | — |
| S18 · S22 · SCB14 · SCB18 | Factory programme | — | Contact us | — |
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | No-load current (%) | Vector group |
|---|---|---|---|---|---|
| 30 | 100 | 630 | 4 | 2.3 | Dyn11 / Yyn0 |
| 50 | 130 | 910 | 4 | 2.0 | Dyn11 / Yyn0 |
| 80 | 180 | 1310 | 4 | 1.9 | Dyn11 / Yyn0 |
| 100 | 200 | 1580 | 4 | 1.8 | Dyn11 / Yyn0 |
| 160 | 280 | 2310 | 4 | 1.6 | Dyn11 / Yyn0 |
| 200 | 340 | 2730 | 4 | 1.5 | Dyn11 / Yyn0 |
| 250 | 400 | 3200 | 4 | 1.4 | Dyn11 / Yyn0 |
| 315 | 480 | 3830 | 4 | 1.4 | Dyn11 / Yyn0 |
| 400 | 570 | 4520 | 4 | 1.3 | Dyn11 / Yyn0 |
| 500 | 680 | 5410 | 4 | 1.2 | Dyn11 / Yyn0 |
| 630 | 810 | 6200 | 4.5 | 1.1 | Dyn11 / Yyn0 |
| 800 | 980 | 7500 | 4.5 | 1.0 | Dyn11 / Yyn0 |
| 1000 | 1150 | 10300 | 4.5 | 1.0 | Dyn11 / Yyn0 |
| 1250 | 1360 | 12000 | 4.5 | 0.9 | Dyn11 / Yyn0 |
| 1600 | 1640 | 14500 | 4.5 | 0.8 | Dyn11 / Yyn0 |
Rated capacity 30 – 1600 kVA. Dyn11 and Yyn0 are both available. Rated capacity 20–2500 kVA is standard. The table lists the ratings with catalogue data; other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) — G1: Grade-1 · G2: Grade-2 | Short-circuit impedance (%) | No-load current (%) | Vector group |
|---|---|---|---|---|---|
| 30 | 80 | G1 550/480 · G2 630/600 | 4 | 1.4 | Yyn0 / Dyn11 |
| 50 | 100 | G1 730/695 · G2 910/870 | 4 | 1.2 | Yyn0 / Dyn11 |
| 63 | 110 | G1 870/830 · G2 1090/1040 | 4 | 0.97 | Yyn0 / Dyn11 |
| 80 | 130 | G1 1050/1000 · G2 1310/1250 | 4 | 0.97 | Yyn0 / Dyn11 |
| 100 | 150 | G1 1265/1200 · G2 1580/1500 | 4 | 0.97 | Yyn0 / Dyn11 |
| 125 | 170 | G1 1510/1440 · G2 1890/1800 | 4 | 0.84 | Yyn0 / Dyn11 |
| 160 | 200 | G1 1850/1760 · G2 2310/2200 | 4 | 0.84 | Yyn0 / Dyn11 |
| 200 | 240 | G1 2185/2080 · G2 2730/2600 | 4 | 0.74 | Yyn0 / Dyn11 |
| 250 | 290 | G1 2560/2440 · G2 3200/3050 | 4 | 0.64 | Yyn0 / Dyn11 |
| 315 | 340 | G1 3065/2920 · G2 3830/3650 | 4 | 0.64 | Yyn0 / Dyn11 |
| 400 | 410 | G1 3615/3440 · G2 4520/4300 | 4 | 0.54 | Yyn0 / Dyn11 |
| 500 | 480 | G1 4330/4120 · G2 5410/5150 | 4 | 0.54 | Yyn0 / Dyn11 |
| 630 | 570 | G1 4960 · G2 6200 | 4.5 | 0.54 | Yyn0 / Dyn11 |
| 800 | 700 | G1 6000 · G2 7500 | 4.5 | 0.48 | Yyn0 / Dyn11 |
| 1000 | 830 | G1 8240 · G2 10300 | 4.5 | 0.42 | Yyn0 / Dyn11 |
| 1250 | 970 | G1 9600 · G2 12000 | 4.5 | 0.36 | Yyn0 / Dyn11 |
| 1600 | 1170 | G1 11600 · G2 14500 | 4.5 | 0.36 | Yyn0 / Dyn11 |
Rated capacity 30 – 1600 kVA. No-load loss Grade-1 and Grade-2 are identical in the factory data; load loss is shown as G1 · G2 (Grade-1 / Grade-2). For ratings up to 500 kVA each pair is upper = Dyn11, lower = Yyn0. Rated capacity 20–2500 kVA is standard. The table lists the ratings with catalogue data; other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 540 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 620 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 720 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 880 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 980 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 1160 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1340 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1300 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1520 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1770 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 2090 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 2450 | 11730 | 6 | D,yn11 / Y,yn0 |
| 2000 | 3050 | 14450 | 6 | D,yn11 / Y,yn0 |
| 2500 | 3600 | 17170 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 480 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 550 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 640 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 790 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 880 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 1040 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1200 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1170 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1360 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1590 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1880 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 2200 | 11700 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2740 | 14400 | 6 | D,yn11 / Y,yn0 |
| 2500 | 3240 | 17100 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 430 | 2130 | 4 | D,yn11 / Y,yn0 |
| 200 | 495 | 2530 | 4 | D,yn11 / Y,yn0 |
| 250 | 575 | 2760 | 4 | D,yn11 / Y,yn0 |
| 315 | 705 | 3470 | 4 | D,yn11 / Y,yn0 |
| 400 | 785 | 3990 | 4 | D,yn11 / Y,yn0 |
| 500 | 930 | 4880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 1070 | 5880 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 1040 | 5960 | 6 | D,yn11 / Y,yn0 |
| 800 | 1210 | 6960 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1410 | 8130 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1670 | 9690 | 6 | D,yn11 / Y,yn0 |
| 1600 | 1960 | 11700 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2440 | 14400 | 6 | D,yn11 / Y,yn0 |
| 2500 | 2880 | 17100 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | Vector group |
|---|---|---|---|---|
| 160 | 385 | 1910 | 4 | D,yn11 / Y,yn0 |
| 200 | 445 | 2270 | 4 | D,yn11 / Y,yn0 |
| 250 | 515 | 2480 | 4 | D,yn11 / Y,yn0 |
| 315 | 635 | 3120 | 4 | D,yn11 / Y,yn0 |
| 400 | 705 | 3590 | 4 | D,yn11 / Y,yn0 |
| 500 | 835 | 4390 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 4%) | 965 | 5290 | 4 | D,yn11 / Y,yn0 |
| 630 (Uk 6%) | 935 | 5360 | 6 | D,yn11 / Y,yn0 |
| 800 | 1090 | 6260 | 6 | D,yn11 / Y,yn0 |
| 1000 | 1270 | 7310 | 6 | D,yn11 / Y,yn0 |
| 1250 | 1500 | 8720 | 6 | D,yn11 / Y,yn0 |
| 1600 | 1760 | 10500 | 6 | D,yn11 / Y,yn0 |
| 2000 | 2190 | 13000 | 6 | D,yn11 / Y,yn0 |
| 2500 | 2590 | 15400 | 6 | D,yn11 / Y,yn0 |
Rated capacity 30–2500 kVA is standard. The table lists the ratings with catalogue data (160 kVA and above); other standard ratings are confirmed in the technical offer.
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Short-circuit impedance (%) | No-load current (%) |
|---|---|---|---|---|
| 50 | 188 | 1210 | 6.5 | 1.8 |
| 100 | 232 | 2010 | 6.5 | 1.9 |
| 125 | 272 | 2380 | 6.5 | 1.7 |
| 160 | 298 | 2860 | 6.5 | 1.6 |
| 200 | 344 | 3330 | 6.5 | 1.5 |
| 250 | 398 | 3960 | 6.5 | 1.4 |
| 315 | 478 | 4780 | 6.5 | 1.3 |
| 400 | 564 | 5740 | 6.5 | 1.2 |
| 500 | 692 | 6880 | 6.5 | 1.1 |
| 630 | 810 | 8280 | 6.5 | 1.0 |
| 800 | 942 | 9640 | 6.5 | 0.9 |
| 1000 | 1150 | 11520 | 6.5 | 0.8 |
| 1250 | 1390 | 13960 | 6.5 | 0.7 |
| 1600 | 1670 | 16860 | 6.5 | 0.6 |
| 2000 | 1940 | 23000 | 6.5 | 0.8 |
| 2500 | 2300 | 27300 | 6.5 | 0.7 |
| 3150 | 2680 | 32900 | 7.0 | 0.7 |
| 4000 | 3240 | 38900 | 7.0 | 0.6 |
| 5000 | 3870 | 46400 | 7.0 | 0.6 |
| 6300 | 4560 | 56200 | 7.5 | 0.6 |
| 8000 | 4810 | 70700 | 7.5 | 0.5 |
| 10000 | 5860 | 83200 | 7.5 | 0.5 |
| 12500 | 6880 | 98400 | 8 | 0.5 |
| 16000 | 7020 | 131700 | 8 | 0.4 |
| 20000 | 8270 | 155700 | 8 | 0.4 |
Rated capacity 50 – 20000 kVA. Short-circuit impedance follows the factory data.
Other series in the factory programme: S18, S22, SCB14, SCB18.
Yes, most capacities and voltage combinations within our stated ranges can be produced within a similar production time. Send us your spec and we will confirm.
Voltage ratio, vector group, capacity and destination.
Last updated: September 22, 2026
When you use our quote tools or contact us we collect the details you give us — name, email, phone/WhatsApp, country/city, your electricity usage and price, company name and any business licence/registration number you choose to provide, plus the content of your messages. When you browse we automatically collect page views, events, device/browser information, an approximate (city-level) location derived from your IP address, and — only with your consent — a pseudonymous analytics identifier stored in a cookie. Read the full privacy policy for the complete list and the purposes.
To prepare quotes, answer enquiries, follow up on orders and installation, improve the website, and meet our legal obligations. We never sell your personal information. Full details.
Essential cookies are needed to run the site. Analytics cookies are only set after you choose Accept all — if you choose Essential only (or close this banner) no analytics cookie is written.
| Cookie | Category | Purpose | Duration | Consent required |
|---|---|---|---|---|
_ga |
Analytics | Tells one visitor apart from another for aggregate traffic statistics. | 2 years by default | Yes |
_ga_JRCS1TC26Y |
Analytics | Keeps the session/visit state for this GA4 property. | 2 years by default | Yes |
We use Google Analytics 4 to measure visits and understand which pages are useful. Google acts as a data processor for us. Your IP address is transmitted to Google so it can derive an approximate location, but GA4 standard properties do not log or store IP addresses. Google signals are not enabled. Event-level data is kept for 14 months in our GA4 property. If you decline analytics cookies, the analytics cookie is not written and analytics storage stays denied.
You can access, correct or delete your personal information, restrict or object to processing, request portability, withdraw consent at any time, and lodge a complaint with your supervisory authority. Contact [email protected]. Full details.
Use Cookie settings (in this banner, at the bottom of every page, or on the privacy policy page) to change your selection — it takes effect immediately.